الوصف
Description
- Wall mounting;
- SensoIRIS B124 standard base mounted;
- Installation wires – 3mm²;
- Cable glands and o-ring protected sealant;
- IP65 according to EN 60529;
- Compatible with SensoIRIS wall sounders.
Installation wires | 3mm² |
Material (plastic), color | ABS, red |
Operation temperature | -10°C ÷ +60°C |
Relative humidity | ≤93% @ +40°C |
Weight | ~140.5g |
Power Supply: From the panel External power supply unit | AUX/GND (24±4)VDC |
Maximum power consumption | 0.11A |
Communication | RS 485 |
Twisted pair cable UTP CAT 5: Maximum length between repeater and panel Cross Section | max. 1000m 0.5-2.5mm2 |
Degree of protection | IP40 |
Color, Material | Grey, ABS |
Operation temperature | -5ºС up to +40ºC |
Relative humidity | up to 95% (without condense) |
Storage temperature | -10ºС up to |
Operating Voltage Range | 15-32VDC (Nom. 27VDC) |
Consumption in quiescent state, no communication | < 130μA@27VDC |
Consumption in quiescent state, with communication | < 180μA@27VDC |
Consumption in alarm state, with communication | 6.5mA |
Output in alarm state at terminal RI (terminals 4/ 1) | 7.5 mA (max)/ 7.5V |
Wire Gauge for terminals | 0.4mm² – 2.0mm² |
Operating temperature | -10°C to +65°C |
Protection | IP30 |
Weight (including base) | ~110g |
Dimensions (including base) | 103x42mm |
Operating Voltage Range | 15 – 32VDC |
Nominal consumption during communication | 220μA |
Relay Parameters | 4A/ 250VAC; 3A/ 30VDC |
Max. current consumption in STAND-BY mode | 175μA@27VDC |
Wire Gauge for terminals | 0.4mm² – 2.0mm² |
Operating temperature | -10°C to +60°C |
Protection | IP40 |
Weight | ~230g |
Dimensions | 142x80x45 mm |