iRIS4
Main Power Supply | 230VAC +10%/-15%,50÷60 Hz |
Back-up Power Supply- lead batteries | 12V/18Ah |
Nominally internal battery resistance | <0,3Ohm |
Storage Temperature | -10˚C to +60˚C |
Operating temperature | -5°C to +40°C |
Dust and moisture protection | IP 30 |
Relative Humidity | up to 95%(without condense) |
Dimensions | 430/330/120mm |
Weight | 6kg(without battery) |
iRIS8
Main Power Supply | 110÷230VAC,50÷60 Hz, 2x200W |
Back-up Power Supply- lead batteries one in the main block + one in the Block expander | 12V/ 18Ah |
Nominally internal battery resistance | <0,3Ohm |
Storage Temperature | -10˚C to +60˚C |
Operating temperature | -5°C to +40°C |
Dust and moisture protection | IP30 |
Relative Humidity (without condense) | up to 95% |
Dimensions | 430/330/120mm |
Weight | Min. configuration 7kg/ Max. configuration 15kg (without battery) |
Repeater
Power Supply: | |
– from the panel | AUX/GND |
– external | (24 ±4)VDC |
Maximum power consumption | 0.11A |
Communication | RS 485 |
Twisted pair cable UTP CAT 5: | |
– maximum length between repeater and panel | max. 1000m. |
– cross Section | 0.5-2.5mm² |
Protection class | IP40 |
Color, Material | White, ABS |
Dimensions of panel | 200x330x48mm |
Maximum number of supported panels in network | 64 |
Network type | Ring topology |
Memory LOG | 10 000 events |
Multi language support | YES |
Operating temperature | -5°C to +50°C |
Relative humidity resistance. | 95% |
Weight | ~ 770g |
SensoIRIS CSOU
Operating Voltage Range | 16 – 32VDC |
Maximal consumption at communication | 470 μА @ 27VDC |
Maximal consumption (main tone type 27: | |
– low volume level | 3 mА @ 27VDC |
– high volume level | 10 mА @ 27VDC |
Power volume: | |
– low volume (up to 100 pcs sounders* to the loop). | ~ 81dB (A) ± 3dB @ 1m |
– high volume (up to 30 pcs sounders* to the loop) | ~ 88dB (A) ± 3dB @ 1m |
Wire Gauge for terminals | 0.4 – 2.0mm2 |
Material and color | ABS / White |
Dimensions | 105 х 22 mm |
SensoIRIS CSST IS
Operating Voltage Range | 16 – 32VDC |
Maximal consumption at communication | 470 μА @ 27VDC |
Maximal consumption (main tone type 27: | |
– low volume level | 3 mА @ 27VDC |
– high volume level | 10 mА @ 27VDC |
Power volume: | |
– low volume (up to 100 pcs sounders* to the loop). | ~ 81dB (A) ± 3dB @ 1m |
– high volume (up to 30 pcs sounders* to the loop) | ~ 88dB (A) ± 3dB @ 1m |
Wire Gauge for terminals | 0.4 – 2.0mm2 |
Material and color | SAN, transparent / White |
Dimensions | 105 х 22 mm |
SensoIRIS GAS
Power supply | 24VDC |
Power consumption | <3W |
Protection against electric shock: | Class III |
Power connection | hard wired |
Alarm threshold | 10%LEL |
Alarms sound level | ≥ 85dB |
Sensor type | catalytic |
Sensor lifetime | 5 years |
Detected gases | LPG/CH4 (Methane) |
Enclosure color | White |
Heating-up time | 30 sec |
Size | 130х96х38mm |
Weight | 0,200kg |
SensoIRIS M140
Operating Voltage Range | 15 – 32VDC (Nom. 27VDC) |
Consumption in quiescent state | < 160μA@27VDC |
Consumption in alarm state, with communication | 6.5mA |
Output in alarm state at terminal RI (terminals 4/ 1) | 7.5 mA (max)/ 7.5V |
Wire Gauge for terminals | 0.4mm² – 2.0mm² |
Operating temperature | -10°C to +60°C |
Protection | IP30 |
Weight (including base) | ~125g |
Dimensions (including base) | 103x42mm |
SensoIRIS MIMIC
Operating voltage | 16 ÷ 32VDC |
Max. current consumption | <2mА @27VDC |
Current consumption with PCB Status LED ON* | 5.4mA |
Operating Voltage | 12÷24VDC |
Voltage for LEDs | 12VDC |
Max current consumption | 390mA@ 24VDC/ 790mA@ 12VDC |
Automatic current limitation of the outputs: With Ri=0k With Ri=1k | 15mA 10mA |
Max. length of connection cable for LEDs | 3m |
Material/color (enclosure box) | ABS, Grey |
SensoIRIS MiniOut
Relay switching power | 60W, 62.5VA |
Relative humidity resistance | (93±3)%@+40°C |
Operating voltage | 15 ÷ 32V DC |
Max. current consumption | 0.1mA |
Relay ratings | 0.25A/24V AC; 2A/30V DC |
Relay rated current | 2A |
Relay max. switching current | 5A |
Protection (with enclosure box) | IP30 |
Relative humidity resistance | (93±3)%@+40°C |
Max. cross section of the cables | 2.5mm2 |
Dimensions (PCB) | 43x25mm |
Mounting | Indoor use |
SensoIRIS MIO04
Operating Voltage Range | 15 – 32VDC |
Consumption, stand-by mode | 175μA@27VDC |
Nom. current consumption | 200µA@27VDC |
Outputs, electrical characteristics (max.) | DC 30V/1A; AC 125V/0,5A |
Wire Gauge for terminals | 0.4mm² – 2.0mm² |
Operating temperature | -10°C to +60°C |
Protection | IP40 |
Weight | ~230g |
Dimensions | 142x80x45 mm |
SensoIRIS S130 IS
Operating Voltage Range | 16 – 32VDC (Nom. 27VDC) |
Consumption in quiescent state, no communication | < 190μA@27VDC |
Consumption in quiescent state, with communication | < 310μA@27VDC |
Consumption in alarm state, with communication | 6.5mA |
Output in alarm state at terminal RI (terminals 4/ 1) | 7.5 mA (max)/ 7.5V |
Wire Gauge for terminals | 0.4mm² – 2.0mm² |
Operating temperature | -10°C to +60°C |
Protection | IP30 |
Weight (including base) | ~125g |
Dimensions (including base) | 103x42mm |