Pressure Reducing Valve
- Pressure Reducing Valve: Reducing a higher upstream pressure into a lower, constant downstream pressure
- Operates over a wide flow range
- Set Pressure is adjustable with single screw
- Can be maintained without removal from the pipe line.
- Flanged to EN1092-2 PN10/PN16, ANSI B16.1 Class 150 FF (Other available on request)
- Grooved Ends to AWWA C606 Standard
- Adjustment Range of Outlet Pressure: 65 to 165 psi
- Rated Working Pressure: 300 psi
- Fusion Bonded Epoxy Coated Interior and Exterior to AWWA C550 Standard.
Pressure Relief Valve
- Pressure Relief Valve: Limits pipe line pressure by release excess pressure
- Pressure sustaining: Prevents pipe line pressure from rising to a maximum value
- Operates over a wide flow range
- Inlet pressure adjustment range: 65-180psi
- Can be maintained without removal from the pipe line
- Flanged to EN1092-2 PN10/PN16, ANSI B16.1 Class 150 FF (Other available on request)
- Grooved ends to AWWA C606 Standard
- Rated Working Pressure: 300 psi
- Adjustment Range of Set Pressure: 65 to 180 psi
- Fusion Bonded Epoxy Coated Interior and Exterior to AWWA C550 Standard.
Zone Control Valve Assembly Accessories
تم تصميم صمامات التحكم في المنطقة لتعمل باستخدام الخدمة الكهربائية للتشغيل. يجب أن يكون نظام الرش قادراً على الإغلاق بعد السيطرة على الحريق، ولإجراء الصيانة والتعديل الدوري. يمكن لصمامات التحكم توفير هذه الوظيفة. في أبسط نظام، يمكن وضع صمام إغلاق واحد عند النقطة التي تدخل فيها إمدادات المياه إلى المبنى.
تتكون الحزمة من: صمام الفراشة، صمام الاختبار والصرف، مقياس الضغط، مؤشر تدفق المياه، مفتاح الإشراف ومؤشر تدفق المياه