مضخات الحريق التوربينية العمودية ذات الطرد المركزي
- All Pumps are Hydrostatically Tested to minimum of 150% of its Maximum Working Pressure and can withstand Double the Max.Working Pressure.
- All Pumps have Clock-Wise Rotation when viewed from the Driver Side.
- All Pumps are Multistage with 2 stages as minimum requirement.
- “The rated speed marked on the pump can vary within +/-4% of the listed/ approved rated speed example: 3000 RPM pump can be driven with 2900 RPM Drivers.”
Model No. | Capacity (GPM) | UL,SETSCO & CE Listed Net Pressure (PSI) | Number of Stages | FM Approved Rated Net Pressure (PSI) | Number of Stages | Approx Speed (RPM) |
---|---|---|---|---|---|---|
SFP-200-70VT | 200 | 40 - 248 | 2 - 12 | 40 - 289 | 2 - 12 | 1480 |
SFP-200-70VT | 200 | 48 - 348 | 2 - 10 | 64 - 348 | 2 - 10 | 1480 |
SFP-200-30VT | 200 | 60 - 305 | 2 - 6 | 2900 | ||
SFP-200-30VT | 200 | 63 - 323 | 2 - 6 | 2980 | ||
SFP-200-30VT | 200 | 64 - 327 | 2 - 6 |