Showing 13–24 of 38 results

SensoIRIS S130 IS

Operating Voltage Range 16 – 32VDC (Nom. 27VDC)
Consumption in quiescent state, no communication < 190μA@27VDC
Consumption in quiescent state, with communication < 310μA@27VDC
Consumption in alarm state, with communication 6.5mA
Output in alarm state at terminal RI (terminals 4/ 1) 7.5 mA (max)/ 7.5V
Wire Gauge for terminals 0.4mm² – 2.0mm²
Operating temperature -10°C to +60°C
Protection IP30
Weight (including base) ~125g
Dimensions (including base) 103x42mm

SensoIRIS T110 IS

Operating Voltage Range 16 – 32VDC (Nom. 27VDC)
Consumption in quiescent state, no communication < 170μA@27VDC
Consumption in quiescent state, with communication < 290μA@27VDC
Consumption in alarm state, with communication 6.5mA
Output in alarm state at terminal RI (terminals 4/ 1) 7.5 mA (max)/ 7.5V
Wire Gauge for terminals 0.4mm² – 2.0mm²
Operating temperature -10°C to +60°C
Protection IP30
Weight (including base) ~110g
Dimensions (including base) 103x42mm

SensoIRIS VAD WST

Operating Voltage Range 20-32V DC (Nom. 27V DC)
Nominal Consumption (stand-by) < 650μA@27V DC
Coverage volume: C-3-6
Maximal Consumption < 19mA
Installation method Ceiling mount
Frequency of the flash beacons 0.5Hz
Color of the LEDs White
Material, color ABS plastic, white (RAL 9016)
Dimensions 122x139x27 mm

SIMPO

Main Power Supply 90 ÷ 264 VAC
Frequency 47 ÷ 440 Hz
Back-up Power Supply 1 battery, 12V/ 18Ah
Electrical output 4.2A
Operating temperature -5°C to +40°C
Weight (without battery) 4.2kg
Dimensions 306x412x81.2mm

SIMPO TTE Loop

Maximum Current Consumption 0.5A
Wire Gauge for terminals 0.4mm² – 2.0mm²
Operating temperature -10°C to +65°C
Weight ~30g
Dimensions 75x80mm

Addressable analog control panel

2 to 8 episodes or 2 to 16 episodes 127 addressable points per SLC loop Single or dual slot (includes area LED module and printer) Modular and expandable electronics 4 programmable NACs; Class B or 2 Class A 7 inch color resistive touch screen with easy to use user interface Power supply options (5.25A or 10.25A) Programmable (3) inputs and (5) relay outputs Networkable with programmable functions Coincidences are OR and AND in cause and effect Programming via USB or PC

Battery operated heat detector

Model No.: LF-HD-42 Attributes Photoelectric technology is more sensitive in detecting large particle fires MCU automatic processing technology Manual test Automatic reset Automatic detection Acoustic light alarm Strong ability to adapt to conditions SMT design, high stability Adopted 9V battery

iRIS8 B

Main Power Supply  110÷230VAC,50÷60 Hz, 2x200W
 Back-up Power Supply- lead batteries one in the main block + one in the Block expander 12V/ 18Ah
Nominally internal battery resistance  <0,3Ohm
Storage Temperature -10˚C to +60˚C
Operating temperature -5°C to +40°C
Dust and moisture protection IP30
Relative Humidity (without condense) up to 95%
Dimensions 660/430/120mm
 Weight 15kg (without battery)

Manual Call Point

Operating voltage 9 ÷ 30 VDC Nominal operating voltage 24 VDC Current consumption in alarm state 23mA/15V; 38mA/24V; 48mA/30V Installation wires 0,4mm2 ÷ 2.0mm2 Operation temperature -10°C ÷ +60°C Relative humidity ≤93% @ +40°C Type of the frangible element A Material (plastic), Color ABS, red Degree of protection IP40 Dimensions (incl. base) 90x57x90mm

Optical – Smoke Fire Alarm Detector

Application

The S30 is a high sensitive optical smoke detector. It is suitable for applications where early detection of smoke or fire is with great importance, for example office buildings, supermarkets, schools, etc.

Relay Output Module

Features

  • Low Profile Design
  • Built-in CPU
  • Fast and Accurate response time
  • Feedback Monitoring
  • Data Transfer Speed and Reliability
  • Polarized Wiring
  • LED Status Indicators
  • High Performance at Low Cost
  • Two Wire System
  • Use LF-DP-6190 for device addressing